High Precision CT PT Analyzer, Automatic Transformer Ratio

High Precision CT PT Analyzer, Automatic Transformer Ratio
Details:
Overview The High Precision CT PT Analyzer, Automatic Transformer Ratio transformer comprehensive characteristic tester is a new generation of current and voltage transformer test instrument developed by our company after extensive listening to user opinions, a large amount of market research,...
Send Inquiry
Description
Send Inquiry

Dual Canopy Mechanic Electrical Engineering Co., Ltd. is one of the leading manufacturers and suppliers of high precision ct pt analyzer, automatic transformer ratio in China. Please feel free to wholesale discount products for sale here and get quotation from our factory. Customized orders are welcome.

 

Overview

 

product-750-750

The High Precision CT PT Analyzer, Automatic Transformer Ratio transformer comprehensive characteristic tester is a new generation of current and voltage transformer test instrument developed by our company after extensive listening to user opinions, a large amount of market research, and in-depth theoretical research. The device adopts high-performance DSP and ARM, and advanced manufacturing technology to ensure stable and reliable product performance, complete functions, high degree of automation, high test efficiency, and is at the leading level in China. It is a professional test instrument for transformers in the power industry.

 

Main technical parameters

 

Test purpose

Protection CT, Protection PT

Output

0~180Vrms, 12Arms, 36A (peak)

CT ratio measurement

Range

1~50000

 

Accuracy

±0.1%

PT ratio measurement

Range

1~50000

 

Accuracy

±0.1%

Phase measurement

Accuracy

±2min

 

Resolution

0.5min

Secondary winding resistance measurement

Range

0~300Ω

 

Accuracy

0.2%±2mΩ

AC load measurement

Range

0~1000VA

 

Accuracy

0.2%±0.02VA

Input power supply voltage

AC220V±10%,50Hz

Working environment

Temperature: -10οC~50οC, Humidity: ≤90%

Dimensions, weight

Dimensions: 340mm x 220mm x 330mm Weight: < 9kg

 

FAQ

 

 

01.What should I do if the device displays an abnormality during testing?

Immediately stop testing, disconnect the device from the power source or remove the battery. Check that the wiring is correct and that the connection is good. If the problem persists, consult the user manual for troubleshooting. Do not disassemble the device yourself and contact a qualified technician for repair.

02.What precautions should be taken when using electrical testing equipment in humid environments?

Ensure that the equipment is waterproof and moisture-proof to prevent water from entering the equipment. Shorten the testing time and dry the equipment surface promptly after testing. Strengthen personal insulation protection to avoid the increased risk of electric shock caused by humid environments.

03.What are the key points of daily maintenance for electrical testing equipment?

Clean the equipment surface and interfaces regularly to avoid debris accumulation. Store in a dry, ventilated environment that is protected from light and shock. Remove the power supply when portable devices are not in use for long periods of time. Check that cables are intact and connectors are secure. Verify basic functionality before and after use.

04.What is the purpose of equipment calibration? What are the consequences of not calibrating on time?

The purpose of calibration is to ensure that the equipment's measurement accuracy meets standards. Failure to calibrate on time can lead to deviations in test data, potentially misjudging equipment status and causing safety incidents. Furthermore, some industries require valid equipment calibration certificates during compliance inspections.

05.How is the calibration cycle for electrical testing equipment generally determined?

The calibration cycle for standard equipment is one year; for equipment used frequently, in harsh environments, or with high precision, this period is shortened to six months. Equipment requires prompt calibration after repairs or severe vibrations. Adjustments can also be made based on the manufacturer's recommendations or industry standards.

06.How should electrical testing equipment be stored when it is not in use for an extended period?

After cleaning the equipment's surface and connectors, place it in a dedicated storage box. Place desiccant in the box to prevent moisture. Remove power components such as batteries to prevent leakage and damage to the equipment. Regularly check the equipment to prevent component degradation.

 

How To Cooperate With Us?

 

Our address

Baoding Cloud Center, Hebei, China

Phone Number/whatsapp

+86 13483219412

E-mail

Salesm@dualcanopy.com

modular-1

Hot Tags: high precision ct pt analyzer, automatic transformer ratio, China high precision ct pt analyzer, automatic transformer ratio manufacturers, suppliers, factory, Volt Ampere Characteristic Tester Current Transformer Test Machine, ct pt analyzers, voltage transformer analyzer ct pt

Send Inquiry