The ultimate goal of the battery charging and discharging tester is to verify whether the battery can meet its designed backup time and power requirements, and to determine its remaining lifespan. The specific functions include:
Capacity Test: The core function. Through constant current or constant power discharge, measure the actual amount of electricity (Ah) or energy (Wh) released by the battery under rated conditions, and compare it with the rated capacity to determine the capacity retention rate (generally considered to be less than 80% of the rated capacity as a reason for replacement).
Performance verification: Test the voltage curve and internal resistance changes of the battery during high-rate discharge to determine its ability to output large currents.
Health status (SOH) diagnosis: By integrating parameters such as capacity, internal resistance, and voltage characteristics, the aging degree and reliability of the battery are evaluated.
Internal resistance test: Measure the AC internal resistance or DC internal resistance of the battery. A significant increase in internal resistance is an early and sensitive indicator of battery aging.
Charging characteristic test: To verify the performance of the charger, or to perform equalization charging and activation repair (for repairable sulfated lead-acid batteries).
Verification discharge: Conduct "live tests" on the backup battery banks in systems such as UPS, DC panels, and communication base stations to ensure their reliable operation in the event of a power outage.
Main types and working principles
Offline (active) charging and discharging tester
Principle: Disconnect the battery pack from the system. Use the tester to provide a constant current or constant power load for discharging. Simultaneously, accurately measure the voltage, current, and time during the discharge process, and automatically calculate the capacity. The discharged energy is usually converted into heat consumption through an energy-consuming load (resistor), or recovered to the power grid or energy storage device.
Work mode:
Constant current discharge: The most commonly used method, with accurate results and easy calculation of capacity (Ah).
Constant power discharge: More closely simulates actual load (such as UPS), and measures energy (Wh).
Constant resistance discharge: Less commonly used.
Programmable discharge: Simulating complex conditions.
Characteristics:
Advantages: High accuracy, comprehensive functions, it is the "gold standard" for capacity testing.
Disadvantages: The testing process takes a long time (requiring several hours), there is a safety risk when the battery pack is disconnected from the system, and there is energy waste (thermal type).
Typical application: Annual or quarterly in-depth inspections of key facilities such as data centers, power plants, and communication rooms.
2. Online (parallel) charging and discharging tester
Principle: The tester acts as a variable load and is connected in parallel between the battery pack and the actual system. During discharge, the battery pack simultaneously supplies power to both the tester (dummy load) and the actual system. The capacity is calculated by measuring the current flowing through the tester and the voltage at the battery terminals.
Characteristics:
Advantages: The battery pack does not need to be disconnected from the system, does not affect the system's backup protection, and the testing is safer and more convenient.
Disadvantages: The accuracy is affected by changes in system load, the calculation is relatively complex, and the cost is high.
Typical application: Non-interruptible backup power supply system.
3. Internal Resistance Tester / Conductivity Tester
Principle: Inject a specific frequency of alternating current signal or a direct current pulse into the battery, measure its voltage response, and thereby calculate the AC internal resistance or the DC internal resistance.
Characteristics:
Advantages: Fast (within a few seconds), loss-free, online testing, suitable for daily inspections and early warning. It can effectively detect severe deterioration of individual batteries (such as loose connections, internal drying, and plate corrosion).
Disadvantage: It is impossible to directly measure the capacity. The relationship between internal resistance and capacity varies depending on the battery type and aging mode, and can only be used as a tool for trend analysis and relative comparison.
Note: Some advanced charge/discharge testers also incorporate internal resistance testing functionality.
4. Capacitor Calibration + Energy Feedback Type Charge and Discharge Tester
Principle: By utilizing advanced PWM and inverter technologies, the discharge energy is converted into alternating current and then fed back to the power grid or supplied to local loads for use, rather than being converted into heat energy.
Characteristics:
Advantages: Energy-saving and environmentally friendly (up to 90% power saving), no thermal pollution, can operate indoors, and the testing cost is extremely low.
Disadvantages: The equipment is complex, expensive, and has an impact on the power grid that requires handling.
Typical application: Large data centers, financial institutions, and other places with strict requirements for energy consumption and indoor environment.