Vacuum circuit breakers are widely used high-voltage electrical appliances in power systems. Their core component is the vacuum interrupter chamber. Since the interrupter chamber operates under vacuum conditions, it is not as easy to assess its quality as oil switches or SF6 switches. Traditionally, the method used by vacuum circuit breaker users to determine the vacuum degree of the interrupter chamber is the power frequency withstand voltage method. This method can only roughly determine the interrupter chamber with severely deteriorated vacuum degree. However, when the vacuum degree deteriorates to 10-2 - 10-1 Pa, although the breakdown voltage does not decrease, the interrupter chamber is already unqualified. Moreover, due to the application of high voltage, it causes damage to the insulation of the vacuum switch. Some manufacturers of vacuum interrupters have already prohibited the use of power frequency high voltage to check the insulation of vacuum circuit breakers.
The vacuum degree tester is a device used to verify the vacuum degree of vacuum interrupters. It operates based on the principle of magnetic control discharge and uses a single-chip computer as the main control unit. The testing process is fully automated. The sampling design of this instrument has changed from the previous method of using the peak current for calibration to using ion charge for calibration. This effectively suppresses the interference from transient power sources during the test, making the test stable and reliable. Due to the use of a computer as the main control unit, this instrument can easily subtract the leakage current caused by environmental factors.
Vacuum gauge
The most prominent feature of the vacuum degree detector is that it enables non-disassembly measurement of the vacuum interrupter chamber, directly displaying the vacuum degree value, allowing users of vacuum circuit breakers to have a detailed understanding of the vacuum state of the interrupter chamber, providing a reliable basis for planned replacement of the interrupter chamber, and offering a strong guarantee for the safe operation of the power grid, overcoming the defect of the power frequency withstand voltage method which can only determine whether the interrupter chamber is scrapped.
Test principle
Pull the two contacts of the arc extinguishing chamber apart to a certain distance, apply a pulse high voltage, wrap the electromagnetic coil around the exterior of the arc extinguishing chamber, and pass a large current through the coil. Thus, a pulse magnetic field synchronized with the high voltage is generated inside the arc extinguishing chamber. Under the action of this pulse magnetic field, the electrons in the arc extinguishing chamber perform a spiral motion and collide with the residual gas molecules to ionize. The generated ion current is approximately proportional to the residual gas density, that is, the vacuum degree. For different vacuum tubes, under the same vacuum degree conditions, the size of the ion current also varies. After measuring the ion current, the vacuum degree is automatically calculated by the computer through the ion current-vacuum degree curve, and the vacuum degree value is displayed.
Test Precautions
The instrument should be reliably grounded.
To improve the measurement accuracy, the outer surface of the vacuum switch should be wiped clean before the test; 3. Please select the type of vacuum tube correctly.
During the test, the high-voltage output terminal will output approximately 30kV high voltage. Please keep the distance between it and the human body as well as the low-voltage line terminals insulated (it is recommended to keep a distance of more than 1 meter from the human body). The magnetic field voltage output terminal will output approximately 400V voltage. Please be cautious!
When conducting the test with the instrument, the wiring should first be connected to the control coil and the vacuum tube, and then connected to the instrument.
After the test is completed, the wires should be removed first by disconnecting the test wires connected to the instrument, then remove the connections to the magnetic control coil and vacuum tubes. If during use you forget to connect the magnetic control coil and directly press the measurement button, immediately turn off the power supply and reconnect the magnetic control coil. Please note that at this time, the output terminal of the magnetic field voltage will have a high voltage. When connecting the wires, do not touch the conductive parts to avoid being injured by the residual voltage on the capacitor.
After the measurement is completed, there may still be residual voltage at the magnetic field output terminal. Please be cautious and take safety precautions.