The arrester counter (also known as the discharge counter) is a crucial accessory for monitoring the number of actions of the arrester and determining whether it is functioning properly. The tests include action reliability tests and counting accuracy tests. Common methods include the DC high-voltage method and the power frequency high-voltage method. The following is the detailed operation procedure and precautions:
I. Preparations Before Testing
Equipment selection
Test power supply: A DC high-voltage generator (with an output voltage range of 0 to 30kV) or an industrial frequency withstand voltage test device can be selected; it should be equipped with a multimeter (for voltage monitoring), grounding wire, and insulating rod.
Check the status of the counter: The appearance is undamaged and free from rust. The connection terminals are secure. The counter dial is clear. The pointer returns to its original position after manual reset.
Surge protector and counter pre-processing
Power outage grounding: Completely disconnect the lightning arrester from the power grid, remove the connections at both ends, and ground and discharge the arrester body and counter for 5 to 10 minutes to release the residual charges.
Clean terminals: Remove the oil and oxide layers from the input terminals (high-voltage terminals) and the grounding terminals of the counter to ensure good contact of the wiring.
Confirm the type of counter: The common types are JC type (electromagnetic) and JS type (electronic). For the electromagnetic type, the action voltage needs to be tested, while for the electronic type, the power supply and signal transmission need to be checked.
Resistor Discharge Counter Tester
II. Core Testing Method (Taking Electromagnetic Counter as an Example)
Method 1: Direct Current High Voltage Method (Commonly used, easy to operate)
Connection method
Connect the positive pole of the DC high-voltage generator to the high-voltage input terminal of the counter (the terminal connected to the high-voltage end of the lightning arrester).
The negative terminal of the DC high-voltage generator is connected to the grounding terminal of the counter (and also connected to the grounding terminal of the lightning arrester).
The multimeter is connected in parallel across the terminals of the counter to monitor the applied direct current voltage.
Test steps
Gradually increase the DC voltage, with the voltage rise rate controlled at 1 to 2 kV/s, and observe the operation of the counter.
When the counter emits a "click" sound and the pointer moves 1 position, record the voltage value at this moment. This value is the action voltage.
Repeat the test 3 to 5 times. After each action, reset the counter. Observe whether the action is reliable and whether the counting is accurate.
After the test is completed, reduce the voltage to 0 first, then disconnect the power supply, and discharge the counter to ground.
Method 2: Power Frequency High Voltage Method (Simulating Actual Operating Conditions)
Connection method
The output end of the power frequency withstand voltage test device is connected to the high-voltage input end of the counter, and the grounding end is connected to the grounding end of the counter.
Series current-limiting resistor (resistance value approximately 10kΩ, power ≥ 50W), to prevent the counter from being damaged by high current.
Test steps
Gradually increase the power frequency voltage until the counter operates, and record the operating voltage.
This method is more in line with the actual discharge conditions of the lightning arrester, but it should be noted that the voltage waveform is a sine wave to avoid harmonic interference.
Method 3: Use the lightning arrester discharge counter tester. According to the user manual, connect the test circuit and you can start the test.
III. Criteria for Eligibility Determination
Action voltage range
The DC operating voltage of the electromagnetic discharge counter should be within the range of 3 to 10 kV (variations may exist among different manufacturers; please refer to the product manual for details), and the deviation of the operating voltage from test to test should not exceed ±10%.
Accuracy of counting
Each time the voltage is applied to the action value, the counter must operate reliably, with the pointer's movement being accurate, without any jamming, omission or over-counting; after resetting, the pointer should return to its initial position.
Additional requirements for electronic counters
Check whether the power supply (battery or external power source) is functioning properly. Replace the battery in time when the battery level is low.
Test the signal transmission function: After the operation, the counting data should be able to be normally uploaded to the background monitoring system.
IV. Safety and Precautions
A safety fence was set up at the test site, and a warning sign reading "High Voltage Hazard" was hung. Unrelated personnel were prohibited from approaching. The operators were required to wear insulating gloves and shoes.
The process of increasing the voltage should be carried out slowly and steadily. It is strictly prohibited to increase the voltage too rapidly, as this may cause voltage overshoot and damage the internal coils or electronic components of the counter.
Before and after the test, it is essential to ensure proper grounding and discharge, especially after the DC high-voltage test. Residual charges may cause electric shock.
During outdoor tests, avoid conducting them during thunderstorms or in damp weather to prevent the test results from being affected by moisture or to avoid the risk of lightning strikes.
If during the test, the counter fails to operate, the operating voltage exceeds the standard range significantly, or the counter gets stuck, the counter must be replaced immediately.