Selection Method And Application Scope Of Loop Resistance Tester

Dec 01, 2025

Leave a message

To select an appropriate loop resistance tester, several key factors need to be taken into consideration comprehensively:
Test current
This is the most crucial parameter. Depending on the different test subjects and standard requirements, select the appropriate output current.
Conventional switchgear: such as circuit breakers, disconnectors, GIS, etc., it is recommended to use a 100A DC test current. This is the most commonly used and recognized standard current in both domestic and international standards at present, which can effectively overcome the measurement error caused by contact electromotive force, and ensure the accuracy and comparability of the data.
High current busbar connection: For large-section busbars and cable joints in power plants and substations, sometimes a test instrument with a capacity of 200A or higher (such as 300A, 400A, 600A) is selected to achieve better test results and anti-interference capabilities.
Micro-ohm level resistance measurement: For the measurement of DC resistance of transformer windings, motor windings, etc., although it also falls under low-resistance measurement, it is usually carried out using a dedicated DC resistance tester. The current selection range of this tester is much wider, ranging from a few amperes to several tens of amperes.
Selection suggestion: For preventive tests in the power system, the 100A standard model is the first choice as it has the strongest versatility.
2. Measurement range and accuracy
Measurement range: Ensure that the instrument's range can cover the resistance value of the device you are testing. Usually, the resistance of the switch circuit is in the range of several tens to several hundred micro-ohms (μΩ), and the instrument's range should be 0-1999 μΩ or wider.
Measurement accuracy: Generally, it is required to be no less than ±(0.5% reading + 0.5% range). The higher the accuracy, the more reliable the data.
Loop Resistance Tester
3. Anti-interference capability
The on-site environment is complex and there are numerous electromagnetic interferences. An excellent testing instrument should have a strong ability to resist industrial frequency interference, ensuring that it can display readings accurately and stably even in a strong electromagnetic field.
4. Type of Technology
Traditional switching power supply type: Mature technology, stable and reliable.
High-frequency switching power supply type: Small in size, light in weight, and high in efficiency. It is currently the mainstream.
Constant current source technology: It can ensure that the current remains highly stable throughout the entire testing process, resulting in more accurate measurement results.
5. Safety and Usability
Long test cable: The standard test cable should be long enough (typically 4-5 meters) and be equipped with insulated special clamps to ensure the safety and convenience of on-site wiring.
User-friendly operation: Large-screen LCD display, with both Chinese and English interfaces, and the operation is simple.
Data storage and output: It has the functions of data storage and retrieval, and supports USB or Bluetooth for data export, facilitating the generation of reports.
Safety protection: It has functions such as overcurrent protection, overvoltage protection, and reverse electromotive force protection.
6. Portability
Consider the size, weight and power supply method (AC/DC) of the instrument. For on-site work that requires frequent movement, a lightweight and portable model is the preferred choice.
Selection Summary:
For the majority of power users, choosing a portable loop resistance tester that outputs 100A of direct current, has a measurement range of 0-1999 μΩ, an accuracy of ±0.5%, strong anti-interference capabilities, a long test lead, and data storage functionality, can meet the daily work needs of over 95% of users.
Scope of Application

The loop resistance tester is mainly used to measure the contact resistance and loop resistance of various conductive circuits. Its application targets include:
High-voltage switchgear:
The contact resistances of the moving and static contacts of various voltage levels of circuit breakers (vacuum circuit breakers, SF6 circuit breakers, oil circuit breakers, etc.).
The contact resistance of the isolating switch and the grounding switch.
The various contact areas within the gas-insulated switchgear (GIS).
Busbar connection area:
The connection points between the busbars in power plants and substations.
Various equipment terminal clips and connection terminals.
Cable lines:
The contact resistance of the cable joints and terminal heads.
Other low-resistance measurements:
Any metal conductive circuit that needs to measure resistances at the micro-ohm level (μΩ).
Core function: By measuring the circuit resistance, it can determine whether there are excessive contact resistances at these connection or contact points due to factors such as loosening, oxidation, erosion, or poor installation techniques. Excessive contact resistance can cause local overheating, accelerate equipment aging, and even lead to serious accidents. It is an important detection method for ensuring the safe operation of the power system.